Parish Status Samples Assessor 1 Assessor 2 System PWS ID System Phone System Address Date/Time Assessment Most Recent Visit System Operational Power Loss Physical Damage Valves Pumps Electrical Storage Tanks Pipes Other Back-Up Generator Generator In Use Fuel Supply Disinfection Type Conventional Treatment PWS Source Population of PWS Immuno-sensitive Populations Servied Response: Isolation Booster Disinfection Increase Free Cl2 Re-routing Water Service Stoped Testing Type Complaints Additional EPA Assistance Requested Date/Time for Update Additional Details
Livingston --- Preston Killcrease Skeeter Vickers Ward II Water District LA1063039 665-5188/665-3474 Corner of Lockhart & Carter Dr. 9/5/05 3:10pm 8/5/2005 Y N N N N N N N Y N N-Manual CLG Y Ground Water 40,800 Y-Hospital,Day Care,Dr. Office,Nursing Home N N N N N Y FC N N Routine-Coliform/1 per month/40 samples;none since hurricane
Livingston Clear Timmy Lemoine Ronnie Sharp Killian, Town of LA 1063030 225-695-6785 9/5/2005 9/3/2005 Y N N N N N N Leaks on distribution N CLG Y Ground Water 900 N N N Y N Y Y FC N N System is up and under pressure.  It had A large leak that was repaired. Searching for a small leak. System has turned up chlorinator,flushed,is under boil notice and waiting to be sampled by DHH
Washington Clear Rusty Reeves Cory Frank Bogalusa LA1117001 985-732-6213 214 Arkansas St. 9/5/05 5:00pm 30 days prior Y N N N DK N N N N Y N CLG N Ground Water 15,000 Y-Dialysis,2 Hospitals,2 Nursing Homes N Y Y N Y Y FC,TC,TCR Y Y-Generators 1Well out of service next to Nursing Home;Pumphouse:2 million gallon tanks out of service-GONE,roof torn off;Wells:Avenue D no backup & tree on control panel,Ave G down 2 days on millitary generator now,North Ave aux engines 1 out of 3;security issues @ 5 sites-fences,etc.;no status known on condition of pumps;6 Fire hydrants torn out-6 main line breaks;3 out of 7 wells out of service greater than 1600ft...NEED:Natural gas generators-150s & fuel
Washington Clear Huey Newcomb Mary T Adams Vornado Water Works LA1117006 985-735-1669 26070 Hwy 21 Angie 70426 9/5/05 5:34pm Y-90% N Y-pressure loss & fixing leaks N N N N Y Y Y Y CLG N Ground Water 1500 services Y-2 schools Y Y Y N Y-24 hours Y FC N Y Wrap Arounds in 3'',2'',4'',6''&8'';Diesel Fuel;Knock Ons in 3'',2'',4'',6'',&8'';Pipe Joints in 6'',3'',4''&8''; 2 rolls 3/4''service pipes;2 boxes curb stops;box meters,box valves;10 saddles of 2'',3'',4'';2 saddles of 6''&8'';2 boxes corporation stops;1 roll 1'' tubing;radios for communication
Washington Clear Huey Newcomb Mary T Adams Boguelusa Water Works LA1117009 735-0005/735-1669 26070 Hwy 21 Angie 70426 9/5/05 5:47pm Y-80% N Y-pressure loss & fixing leaks N Unsure about booster station-tree damage N N Y Y Y Y CLG N Ground Water 1300 taps y-Prison,Dialysis, 2 schools Y N N N Y-24 hours Y FC N Y 150 Cb cylinders chlorine-Davis Project;Diesel Fuel;12'' Wrap arounds in 3'',2'',4'',6''&8'';Knock ons in 3'',2'',4'',6'' & 8'';Pipe Joints 6'',3'',4''8'';10 saddles in 2'',3'',4'';2 saddles in 8'' & 6'';2 rolls 3/4'' service pipes;2 boxes curb stops;box meters;box valves;2 corproation stops;1 roll 1'' tubing;radios for communication
Washington Clear Juliun Formea Angie Water Supply LA1117008 985-986-2444 64475 Cherry St.  Angie 70426 9/5/05 4:56pm Y Y N N N N N 5 busted lines-all repaired Y Y Y CLL N Ground Water 400 1 school N N N N N Y FC-Daily Y-low pressure Y Diesel for generators;12 ''dresser couplings in 11/2'',11/4'',2'' & 1''
Tangipahoa GENLP Jason Dean Dean Studer Dave's MHP LA1105042 985-345-3637 9/5/05 3:45pm Y Y N N N N N N N CLL Y Ground Water 418 N N N Y N Y pH,FC,TC,A,T,TCR N N
Livingston GENLP Timmy Lemoine Steve Parrill Springfield Middle School LA2063033 225-294-3306 PO Box 40 Springfield  70462 9/5/05 4:00pm 5-May Y N N N Chlorine Pump N N N N CLL Y Ground Water 425 N N Y Y N DK DK FC N N System chlorinator pump was out of service but is back in service. System was flushed, and bacti sample will be taken on 9/6/05
Livingston GENLP 9/7/2005 Bill Chavmont Molly Patton Walker, Town of LA1063017 225-665-4356 12923 pleasant ridge Walker 70785 9/5/2005 Y N N N N N N N Y N Y CLG Y Ground Water 5000 DK N N N N N Y FC,TC N First and last month Bactis, 15 sites, one each month. 3 wells are in operation, well #4 was on a generator for 3 days-Mon-Wed,back on power Thurs. Well #2-security fence-chlorine signs,TMB461-phoshate amonia, was not flooded,gas chlorination,production 550gal/min.Well #3-Production 600gal/min, gas chlorine,TMB461-designing root system developing auto switch for supplimental power,panomedric meters in use now, operator plans to replace with something more convenient to read.Well#4-production 1250gal/min, gas chlorination, best producer.Well #1 abandoned long ago PNA.Recently added TMB461(3 Months)notices customers commenting on cleaning up the water.
Livingston GENLP 9/6/05-4 Charles Barnes Fourth Ward Water Works LA1063005 225-209-9333 Albany 9/5/2005 3:00pm Y-No pressure loss - - N N N N N Y Y CLG Ground Water DK DK N N N Routine N Spoke to Sid Kinchen by telephone.15,000 not damaged.4 samples to Amite
Livingston GENLP Ken Rasini Lloyd Lepretre Dehnam Springs LA1063004 225-667-8351 27135 Hwy. 16   Dehnam Springs, 70726 9/6/05 9:20am Y 15 150 motor is not running having one on order, which caused one well to be down. Y-on generator 4 hrs. for two wells N CLG Ground Water 27,600 N N Y N N N Y FC,TC N N Has 5 wells that have 2 towers. One well has motorburnt out, expects to replace today. Never lost below 50psi. 2 wells ran on intermitent generator for 4-5 hrs. Never had a boil order. At first test sight-far end on south:total=1.4ch,free=1.1fr.  At 2nd test sight-middle of system:total=1.6,free =1.0.  At 3rd test sight-north side end of line:total=1.2,free=1.0.  Main concern people calling for chlorine,he has enough for next week,supposed to have 10 bottles coming in today if he gets it he will be set for a month-not giving any away. Has offered manual assistance to anyone that need's it.  Just call has spare parts for chlorinators,etc.  (Spoke with Johnathan Johnson-Superintendant),
Livingston GENLP 9/6/05-4 Curtis Edgar Tommy Taylor Albany, Village of LA1063022 225-567-1101 PO Box 1000   Albany,70711 9/6/2005 Y N CLG Ground Water 3,500 N N N Y N N N Y-air in water N Checked chlorine free residual 9/5/05 and it was .05.
Tangipahoa GENLP Guy Dietrich Richard Skyles Tickfaw, Villahe of LA1105026 985-542-9249 50081 Hwy. 51   Tickfaw, 70466 9/6/05 2:30pm August, 2005 Y N N CLG N Ground Water 1300 N N N Y-1.5 to 2 N FC N Y Doing routine testing.  NEED 125 KW Generator. 2800 ft well, pressure was below 20.  Town only has one well and one truck, no other back-up wells or trucks.  Mr. Lamonte asked near-by water system to purchase water to fill his tank during an emergency.  This other water system is three feet away.  His request to purchase water was denied for fear of loss of pressure.  A borrowed generator ws used after the hurricane.
Livingston GENLP 9/6/05-6 Allen Anderson Ken Terry Livingston, Town of 1063013 225-686-7153 P.O. Box 430 Livingston, LA  70754 09-05-05 / 4:30 PM Y Y N - - - - - - Y N Y CLA/CLG N Ground 5668 DK Y N N N N Y TC N N Clear never lost pressure
Livingston GENLP 9/6/05-2 Allen Anderson Ken Terry Colyell Community Water System 1063003 225-698-3739 P.O. Box 392 Livingston, LA  70754 09-05-05 / 3:20 PM Y - - - - - - - - Y N DK CLA/CLG N Ground 2272 DK N N DK DK N Y FC N N Never loss pressure or Cl2
Washington GENLP Margaret Beckman - Mt. Hermon Water District 1117021 800-375-7570 - 09-05-05 / 4:45 PM - - - - - - - - - Y Y N CLG Y Ground 1944 DK Y Y DK N Y Y FC Y N Cl2 @ Mt. Hermon Fire Dept.- Free 0.5/Total 0.6; Having trouble getting fuel; 1 complaint about taste
Tangipahoa GENLP Eugene Bradley Jon Lam Intersection Connection 1105086 985-429-8135 414 84 W-I55 Service Road Lot 14 09-05-05 / 4:45 PM Y - N - - - - - - Y N - CCL N Ground 20 Connections DK DK N N N DK - FC & TC - N Became operational today;Power back on;Generator not used constant. Only to provide water in mornings & during outage;Periodic usage during outage via generator;Recommended elevaing Cl2 level to 1.0-2.0 ppm for 24 hrs. Sample after disinfection process;Samples needs to be collected
Tangipahoa GENLP Eugene Bradley Jon Lam North Oaks Medical Center 2105051 985-345-2700 15790 Paul Vega MD Dr. Hammond, LA 70403 09-05-05 / -- Y - N - - - - - - Y N Y CLG - Ground 245 Beds & 1500 Employees Y DK N N N N - FC N N Keeps 72 hrs of diesel at a time; Corrosion Control; Free Cl2 has been between 0.3 & 0.4 ppm; Was not able to meet with maint. Personnel.Spoke w/ Russell Hoover via phone.Was not able to inspect system; Free Cl2 reading 0.3 ppm
Tangipahoa GENLP Sandra Atwood S. Guy Dietrich Pontchatoula, City of 1105019 985-320-2446 380 N. Fourth Street 09-05-05 / 3:45 PM Jul-05 Y - - - - - - - - Y N - CLG N Ground 5,500 N N N N N N Y FC N N Lost power-generator kicked in. Pressure OK; Power back Wednesday afternoon
Tangipahoa GENLP Alvin Moss   Tickfaw, Village 1105027 985-542-9249 5001 Hwy 51 North Tickfaw, LA 70466 09-05-05 / 4:00 PM Same Y - - - - - - - - Y N DK CLG Y Ground 1,100 DK N N N N N N - DK N NONE Never lost pressure, low pressure due to electrical problem. Problem resolved. Biggest problem communication; System's Contact - Dave Simoneaux 985-345-4677
Livingston GENLP Allen Anderson Ken Terry Livingston, Town of 1063013 225-686-7153 P.O. Box 430 Livingston, LA  70754 09-05-05 / 4:30 PM Y Y N - - - - - - Y N Y CLA/CLG N Ground 5668 DK Y N N N N Y TC N N Clear never lost pressure
Livingston GENLP Allen Anderson Ken Terry Colyell Community Water System 1063003 225-698-3739 P.O. Box 392 Livingston, LA  70754 09-05-05 / 3:20 PM Y - - - - - - - - Y N DK CLA/CLG N Ground 2272 DK N N DK DK N Y FC N N Never loss pressure or Cl2
Washington GENLP Margaret Beckman - Mt. Hermon Water District 1117021 800-375-7570 - 09-05-05 / 4:45 PM - - - - - - - - - Y Y N CLG Y Ground 1944 DK Y Y DK N Y Y FC Y N Cl2 @ Mt. Hermon Fire Dept.- Free 0.5/Total 0.6; Having trouble getting fuel; 1 complaint about taste
Tangipahoa GENLP Eugene Bradley Jon Lam Intersection Connection 1105086 985-429-8135 414 84 W-I55 Service Road Lot 14 09-05-05 / 4:45 PM Y - N - - - - - - Y N - CCL N Ground 20 Connections DK DK N N N DK - FC & TC - N Became operational today;Power back on;Generator not used constant. Only to provide water in mornings & during outage;Periodic usage during outage via generator;Recommended elevaing Cl2 level to 1.0-2.0 ppm for 24 hrs. Sample after disinfection process;Samples needs to be collected
Tangipahoa GENOK Eugene Bradley Jon Lam North Oaks Medical Center 2105051 985-345-2700 15790 Paul Vega MD Dr. Hammond, LA 70403 09-05-05 / -- Y - N - - - - - - Y N Y CLG - Ground 245 Beds & 1500 Employees Y DK N N N N - FC N N Keeps 72 hrs of diesel at a time; Corrosion Control; Free Cl2 has been between 0.3 & 0.4 ppm; Was not able to meet with maint. Personnel.Spoke w/ Russell Hoover via phone.Was not able to inspect system; Free Cl2 reading 0.3 ppm
Tangipahoa GENOK Sandra Atwood S. Guy Dietrich Pontchatoula, City of 1105019 985-320-2446 380 N. Fourth Street 09-05-05 / 3:45 PM Jul-05 Y - - - - - - - - Y N - CLG N Ground 5,500 N N N N N N Y FC N N Lost power-generator kicked in. Pressure OK; Power back Wednesday afternoon
Tangipahoa GENOK Alvin Moss   Tickfaw, Village 1105027 985-542-9249 5001 Hwy 51 North Tickfaw, LA 70466 09-05-05 / 4:00 PM Same Y - - - - - - - - Y N DK CLG Y Ground 1,100 DK N N N N N N - DK N NONE Never lost pressure, low pressure due to electrical problem. Problem resolved. Biggest problem communication; System's Contact - Dave Simoneaux 985-345-4677
St. Tammany GENOK Bill Chaumont Bruce Hawkins Mandeville Water Supply 1103023 985-624-3169 3101 E. Causeway Approach, Mandeville, LA 70448 9/5/2005 y - - - - - - - - Y N CLG Ground 13,000 DK N N N N N Y - N N NONE 5 well & one elevated storage tank, pop 13,000, 10 samples taken on 9-5-05, sent to Aimete, Chlorine residuals:  Free 0.82 ppm, Total 1.81 ppm, polyphosphates added, System has generators for all wells, One well #1 has also gas drive.
St. Tammany GNLP Ken Terry Allen Anderson Tulane University Primate Center 2103216 985-871-6210 18703 Three Rivers Road, Covington, LA 70433 9/6/2005 / 2:00 pm Y - - - - - - - - Y Y Y NONE N Ground 200 N N N N N N N - N N System is on, back up generator, Never loss pressure, does not chlorinate
St. Tammany GNOK Ken Terry Allen Anderson Tchefuncte Club Estates 1103043 985-892-3045 #2 Pine Crest Dr., Covington, LA 70433 9/6/05 / 11:45 am - - - - - - - - Fence N N N NONE N Ground 1360 DK N N N N N N TC - - - System is running on well pressure, Well gauge is at 23 PSI, System need s repairs on fence and generator for well and booster pump.  System also will need a chlorinator if fails bacti sample
Tangipahoa GNOK Jason Dean Dean Studer Fluker Chapel Water District LA1105005 985-748-6339 9/6/05 10:45am N Leaking at top of wellhead (another well) N DK Ground Water 296 DK N Tree has fallen near well head broken piping loose and pulled power lines down on chain link fence and smashed fence.  Called EOC, talked to Kathy-informed them that power lines are down on chain link fence and to clean up fallen tree before lines are energized. Was surveyed by Eugene & Jon same day met w/owner -Tangipahoa WD coded INOP
Tangipahoa GNOK Y Jason Dean Dean Studer Kentwood, Town of LA1105014 985-229-3541 308 Ave. G 9/6/05 11:50am Y Y N 12'' N N CLS Y Ground Water 2000 N Y N Y N Y Y pH,FC N N Sample taken 9/5/05 waiting on results. Need a new generator. Old one burned up.
Tangipahoa GNOK 9/8/2005 Jason Dean Dean Studer Tangipahoa,Village of LA1105026 985-229-8300 101 Jackson St. 9/6/05 11:00am Y Y Y Model SK256DP6008JT382282.3 phase,60hertz,1.15 service falter,Hp20,Rpm1755,Volts 230/460,amp50 2/25.1,frame L256TP12,degrees C40, MaxAmb Master meter main upright tank not stable shaft on well head is loose Y N Y CLL Y Ground Water 1100 N Y N Y N Y Y FC,TC N N Need follow-up with LRWA. Take sample Thursday
Tangipahoa GNOK Eugene Bradley Jon Lam Fluker Chapel Water District LA1105005 985-386-6457 PO Box 694  Natalbany 70451 9/6/05 2:30pm N Y Y Well N CLL Y Ground Water 40 connections DK N Y Contact Gary Clark, manager Tangipahoa WD about assistance . Bulk water needed for residents w/o water service.  Possability that Iron is accumulating in the Hydpn tank and is affecting water color according to a resident. Reportedly had no water before damage from KAtrina.
Tangipahoa INDP Alvin Moss Tom Schlife Hammond High School LA2105094 985-748-2490 River Rd. Hammond, 70401 9/6/2005 11:50 Y Y N N CLL Y Ground Water 1300 N N Y Y N Y N N N
Tangipahoa INOP Alvin Moss Tom Schlife Hammond Heights LA1105010 9/6/2005 Y DK DK N N N None seen N Ground Water DK DK DK DK DK DK DK DK N No operator available for assessment. There does not appear to be any damage to the wells or system. There is no visible form of disinfection at the well sites.
Tangipahoa INOP Alvin Moss Tom Schlife City of Hammond LA1105009 985-542-3525 PO Box 2788  Hammond,70404-2788 9/6/05 10:30am Y N N Well #1 security fence down Y N Y CLG Y Ground Water 18,000 N N N N N N Routine N N Contact person=Garry Knight Supt W/S
Tangipahoa INOP Edwin Vazquez Jack Horton Roseland, Town of LA 1105022 985-748-9063 62438 Commercial St.  Roseland, 70456 9/6/2005 Y N Y Y CLG Ground Water 2600 DK N DK DK N N Y FC N Y Went to electric generator, never lost pressure.
Tangipahoa INOP Edwin Vazquez Jack Horton Blue Crystal MHP LA1106088 985-878-9793 55308 Mashon Rd, Independence, 70443 9/6/05 11:28am Y N CLL 60 DK N DK N Y Y N N Sample readings:free=0.6,total=0.7. As a Contract operator takes came of bleach feed and chlorine testing.
Tangipahoa INOP Edwin Vazquez Jack Horton Viola MHP LA1105084 985-878-9793 55533 Durbin Rd.  Independence, 70443 9/6/05 11:30am N Y N N ClL Y Ground Water 36 DK N DK N N Y Y FC N Y System is down due to electrical outage.  A generator is needed until electricity is returned.
Tangipahoa INOP Eugene Bradley Jon Lam Tangipahoa Parish W.D. LA1105008 985-386-6457 PO Box 699  natalbany, 70451 9/6/05 1:00pm Y CL2 booster pump@ demarco well(replaced w/backup) 8" main @ Hwy 22 West Fence damage @ Dutch well Y-@Honetsuckle,Dutch,Thorn,Wal-Mart (7 wells/4 generators Y-@Wal-Mart &Thorn Y CLG Y Ground Water 9620 connections DK N N N N N Routine FC,TC,TCR N N Name change to Tangipahoa Water District (Parish should be remover from name),3/4 ton Chevy Van (2005), Need generator @ Woodhaven (generator out of service-60KVA),no generator @ Demarco (need 80 KVA gen), no generator @ Baptist (100 to 125 KVA) needed for booster CL2 system (also chemical feed pumps)-auxillary drive &portable generator were used,8" main on Hwy 22 West damaged by falling tree (note lines were looped-both sides of lines were ***repairs done under pressure.
Tangipahoa INOP Eugene Bradley Jon Lam Tangipahoa 2nd Ward W.D. LA1105077 985-386-6457 PO Box 699 Natalbany, 70451 9/6/05 1:45pm Y service poles down @ Lewiston #1 4" on Wilson R J Hyllary Simmons Fences damaged Lewiston 1g2 Y-Lewiston #1 Y Y CLG sodium ash(pH),phosphate:corrosion control Ground Water 1129 connections DK N N N N N pH,FC,A N N Broken lines were repaired hot.
Tangipahoa INOP Eugene Bradley Jon Lam Manchac LA115096 985-386-6457 PO Box 699  natalbany, 70451 9/6/05 2:15pm N Y N CLL Y Ground Water 2 connections-restaurant & 1 resident DK Assessing N Need generator (40 KVA)
Tangipahoa INOP Guy Dietrich Richard Skyleh Westview Water District LA1105028 985-748-8488 Hwy 16 & 1046 9/6/2005 Last year-2004 Y Y-automatic switch-over,pressure never lost N N N N N N N Y Y Y CLG N Ground Water 1500 N N N-chlornation one time from five to seven pounds just to be safe Y N N Y FC N N Routine water testing every three years.
Tangipahoa INOP Guy Dietrich Richard Skyleh Eastern Heights Water Works LA1105003 985-748-4510 Hwy 16 east on Leander ln 9/6/05 12:30pm Y power outage N Y-borrowed Y CLG N Ground Water <2500 N N N N N N Y FC Y-low water pressure N Joe states his needs would be a back-up power generator. Routine testing
Tangipahoa INOP Guy Dietrich Richard Skyles French Settlement-Blackcat LA1105025 225-952-7602 Blackcat Rd. & Hwy 51 Tickfaw 9/6/05 1:30pm DK Y Y N N CLG N Ground Water 1768 N N N N N Y FC N N No needs at this time.Samples taken by company,came back clean. State Total Chlorine
Tangipahoa INOP Guy Dietrich Richard Skyleh French Settlement Bankston LA1105036 225-952-7602 Bankston Rd, Amite 9/6/2005 DK Y Y N N CLL N Ground Water 164 N N N N N Y Y pH N N State does total coliform. No needs. They plan to take their own samples and deliver to the Milk Lab, in the next couple of days.
Tangipahoa INOP Guy Dietrich Richard Skyleh French Settlement Velma LA105078 225-952-7602 Hwy 16 & Independence 9/6/2005 Y Y N N CLG N Ground Water 1408 N N N N N Y Y pH N N State does Total Coliform. 
Livingston INOP Perry Cowart Dave McMillan Cliffs Campsites LA1063112 225-695-6447-Anita Silvernail 9/6/05 5:00pm-phone contact Y N-temporary emergency back-up generator used N N CLL Ground Water DK Y FC,TC,TCR N N Power loss/restored power (ran off generator),may not have lost pressure. No immediate need. Long term will be a permanent back-up power source.
Livingston INOP Perry Cowart Dave McMillan Vincent Place Residents LA1063041 9/5/2005 Y n-temporary generator if needed N N CLL Y Ground Water Y N Y Y FC,TC,TCR N N Lost Power/restored power/D.I./Flushed/resumed operation/sample. N o immediate need. Long term-back-up power source
Livingston INOP Patti Broussard Kirbys Place LA1063072 Removed as a system, not evaluated see notes:1. Chlorination being done;2. No complaints received; 3. Assumption is system is operating
Livingston INOP Raymond Ernest Dave McMillan Cline Subdivision LA1063051 225-673-8560-Patricia Vulega 9/6/05 3:00pm Y Y-as needed Y Y CLS Ground Water N N System remained in operation. Back-up generator activated.
Livingston INOP Raymond Ernest Dave McMillan Chinquapin LA1063114 225-673-8560-Patricia Vulega 9/6/05 3:00PM Y Y-as needed Y Y CLS Ground Water DK N N System remained in operation. Back-up generator activated.
Livingston INOP Raymond Ernest Dave McMillan Three Rivers Island LA1063111 225-673-8560-Patricia Vulega 9/6/05 3:00pm Y Y-as needed Y Y CLS Ground Water DK N N System remained in operation. Back-up generator activated.
Livingston INOP Raymond Ernest Dave McMillan Bayue Terrace-River Highlands LA1063109 225-673-8560-Patricia Vulega 9/6/05 3:00pm Y Y-as needed Y Y CLS Ground Water DK N N System remained in operation. Back-up generator activated.
Livingston INOP Raymond Ernest Dave McMillan Water Front West LA1063104 225-673-8560-Patricia Vulega 9/6/05 3:00pm Y Y-as needed Y Y CLS Ground Water DK N N System remained in operation. Back-up generator activated.
St. Tammany Need Ken Terry Allen Anderson St. Tammany Water Dist #3 1103056 985-892-3045 PO Box 1478, Covington, LA 70434 9/6/2005 / 9:30am Y - - - - - - - - Y Y Y CLG - GROUND 2920 DK DK N N N N Y FC/TC N N System is operating on backup generator. One well is not operating but has maintained pressure & chlorine from main well
St. Tammany Need 9/6/2005 BILL CHAUMONT BRUCE HAWKI Madisonville Water Supply 1103022 985-845-7311 PO Box 160, Madisonville, LA 70447 9/6/2005 / Y - - - - - - - - N N/A N/A CLG N GROUND 700 DK N N Y - Y Y FC N N Two wells:  North & South, Chlorine residuals.  Well #1 (Johnson & Hwy 22) -artesian - flowing but can not chlorinate.  Under boil order.  350 pop served.  Total pop served - 700.  Well #2 - (Pine 2) running w/power & chlorination.  System never lost pressure below 20 psi even when without power.  The system was split for a period of time.  But is now open. 
St. Tammany NEED 9/6/2005 BILL CHAUMONT BRUCE HAWKI BEAU CHENE WATER SUPPLY 1103006 985-845-3565 817 BEAU CHENE, MANDEVILLE, LA 70471 9/6/2005 Y Y Y FENCE WELL 3 - - - - - Y Y N/A CLG Y GROUND 4700 DK N N - N N - - N N Property manager, Bill Maier - Add polyphosate concentrate & monitor control.  TC - 1.40ppm, FC - 0.65 ppm, TC - 0.35ppm, FC - 0.19 ppm - Fencing on perimeter of well #3 is damaged.  System lost pressure <15 psi for 3-4 hourse.  Chlorination on Well #4 & serving entire system.  Diesel generator running water well. 
St. Tammany NEED 9/6/2005 SKEETER VICTORS KAREN ENGEBRESTOON FOLSOM WATER SUPPLY 1103014 985-796-5017 PO BOX 609, FOLSOM, LA 70437 9/6/05 / 10:30AM Operation on site Y - - - - generator with bad contacts in panel box - online pulled out - is repaired - N Y N CLG - GROUND 1686 Y N Y Y N N Y FC N Y Electrician to repair lift stat, back up generator, control panel for generator, need generator for city operations, 2 lift stations for wate water system off, meter panel off post - not operating.  Fuel supple short, no pump to pump fuel. 
St. Tammany NEED 9/6/2005 SKEETER VICTORS KAREN ENGEBRESTOON Southeastern LA state Hospital 1103039 985-626-6315 Hwy 190 East, Mandaville, LA 70472 9/6/05 / 1:10 pm Y - - - - - - - - Y Y Y LSH - GROUND 200 Y N N N N N N - N - Need to treat and flush the system.  2 sample Poc 2, Poc 4.  No treatment, chlorine empty have barrel on hand. Need to move into location. 
St. Tammany Need GREG ARABIE TOWN OF PEARL RIVER 1103157 985-863-5800 PO BOX 1270 9/6/2005 / 10:00 AM Y Y some lines broken - - N/A n/a n/a - y N/A y CLG N GROUND 3000 N N N Y N Y Y FC N N System back up in normal power samples taken of 9/2/05 waiting on result form DHH, System did inform customer to boil water for use until results from DHH.  Samples taken as precaution. 
Washington Need RONNY STEELE CHRIS BROWN PALMS TRAILER PARK 1117023 29 PALMS TRIALER PARK 9/6/2005 - - - - - - - - - - - - - - - 25 - - - - - - - - - - - Water is out owner lives in Pine, No contact - one resident, 5 people - one trailer.  Major damage, minor damage to other trailer. 
Washington Need 9/6/2005 DAVID CRAIN CHRIS BROWN/LONNY STEELE DAIRY FARMERS OF AMERICA 2117174 985-839-4481 21155 Hwy 16, FRANKLINTON 9/6/2005 / 11:40 TWO WEEKS Y - - - - - - - - Y Y Y NONE N GROUND 50 N N N N N N N - N N - 2 wells only one run at any one time.  Will take 2 samples today (324203, 324205), have certified milk test lab, water test capable in lab.  No chlorination/no residual taken.
Washington Need GERALDS WOOD GERALDS STEAK HOUSE 2117100 9/6/2005 N Y DK - - - - - - - - - - - - - - - - - - - - - - - - -
Washington Need 9/6/2005 Jimmy Stewart STEWARTS SEAFOOD AND STEAK 2117136 839-9616 16424 HWY 450 9/6/05 / 1:30pm Y Y - - - - - - - Y N/A - LSH N GROUND 125 N N N Y N Y - FC - - generator not operable, out sun - wed right after storm, bought generator on wed.  Took sample to amite labs
Washington NEED CORY FRANK RUSTY REEVES COUNTY GENERAL 2117192 9/6/05 / 2:50PM - - - Y - - - - - - - - - - - - - - - - - - - - - - - - pump house damage
Washington NEED CORY FRANK/RUSTY REEVES JOETTA THOMAS JO'S PLACE 2117190 9/6/2005 Y Y WELL STATION - - - - SECURITY N N/A - - - - - - - - - - - - - DK N - Need generator and fuel, No electric, gas, dump for debris, phone
Washington NEED CORY FRANK/RUSTY REEVES NEIL LEDET THOMAS GROCERY 2117131 985-848-5501 31042 HWY 424, FRANKLIN 9/6/2005 30 DAYS Y Y Y OK OK OK OK 3/4'' service lines - n - - LSH N GROUND - Y Y N N N Y N - N N - Request - ice, fuel, need generator, not selling or distributing to unknown public.
Washington NEED LINDA GRAVES WARNERTON QUICK STOP 2117186 985-795-1924 32011 HWY 25, FRANKLINTON 9/6/2005 / 12:07 Y Y DK - - - - - - Y Y Y LSH N GROUND N N N N N N N - N N Cost inventoy of ice cream $300, inventory of deli food $700, system not disinfecting, only selling non perishable foods only usin gwater for comode
Washington NEED CORY FRANK/RUSTY REEVES LANDON KNIGHT BIGS PLACE GROCERY 2117149 - 53148 HWY 438, FRANKLIN 9/6/2005 30 DAYS N Y Y - - CHLORINATIN PUMP - YES - N - - LSH N GROUND N N - - - - - - N - - Security compromise, fence damaged, back up generator, fuel, food and water critical. 
Livingston NEED Perry Cowart Bogan Village Trailer Park 1063094 800-375-7570 09/05/05 / PM Y - - - - - - - - N N N CLL - Ground - DK - - Y N Y Y FC,TC,TCR N N French Settlement Wtr Co;Bleach;Lost power/restore power/chlorinate/flush/resume operation/sample;No immediate threat; Long term backup generator
Livingston NEED Perry Cowart Highland Ridge Subdivision 1063087 225-766-4477 09/05/05 / PM Y - - - - - - - - N N N CLL - Ground - DK - - - N Y Y FC,TC,TCR N N - Total Env. Sol. Inc.;lost power/restore power/chlorinated/flushed/resumed operation/sampled;No immediate need; Long term-backup generator needed.
Livingston NEED Perry Cowart Pine Heaven Estates 1063089 800-375-7570 09/05/05 / PM Y - - - - - - - - N N N CLS - Ground - - - - - N Y Y FC,TC,TCR N N Lost power/restored power/DI/flushed/resumed operation/sampled;No immediate need; Long Term-Backup Power source needed.
Livingston NEED Perry Cowart The Cove 1063117 225-673-8560 09/05/05 / PM Y - - - - - - - - N N N CLL - Ground - DK - - - N Y Y FC,TC,TCR N N Patricia Valega;Temporary generator brought in;May not have lost pressure; temporary generator brought in; lost power/restored power/return to operation; No immediate need; Future need-permanent back up ower source
Livingston NEED Perry Cowart Old Mill Settlement 1063115 225-673-8560 09/05/05 / PM - - - - - - - - - N N N CLL - Ground - - - - Y N N Y FC,TC,TCR N N - patricia Valega;Temporary generator brought in;May not have lost pressure; temporary generator brought in; lost power/restored power/return to operation; No immediate need; Future need-permanent back up Power source
 - - NEED  - - Al Moss Tom Schlife Silessi MHP LA1105056 985-345-8518 42419 GreyDr 9/7/2005  - - Y Y  - -  - -  - -  - -  - -  - -  - - N N N CLL N GW 350 N Y N N N N  - -  - - N N  - -  - -
  - - NEED  - - Richard Skyles Gery Dietrich Coleman Trailer Park LA1105060 225-567-3148 south Baptist & Coleman Park 9/7/2005  - -  - -  - -  - -  - -  - -  - -  - - -  - -  - -  - -  - -  - -  - -  - -  - -  - -  - -  - -  - -  - -  - -  - -  - -  - -  - -  - -  - - Hooked on to the District system;no well;